APC Smart-UPS XL, 2700 Watts / 3000 VA,Input 208V / Output 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model
| Technical Specifications |
Technical Details |
| Output |
| Output Power Capacity |
2700 Watts / 3000 VA |
 |
| Max Configurable Power |
2700 Watts / 3000 VA |
 |
| Nominal Output Voltage |
208V |
 |
| Efficiency at Full Load |
96.00% |
 |
| Output Voltage Distortion |
Less than 5% at full load |
 |
| Output Frequency (sync to mains) |
47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal |
 |
| Crest Factor |
up to 5 : 1 |
 |
| Waveform Type |
Sine wave |
 |
| Output Connections |
(2) NEMA L6-20R |
 |
| (2) NEMA L6-30R |
 |
| Input |
| Nominal Input Voltage |
208V |
 |
| Input Frequency |
50/60 Hz +/- 3 Hz (auto sensing) |
 |
| Input Connections |
NEMA L6-20P |
 |
 |
| Cord Length |
6 feet (1.83 meters) |
 |
| Input voltage range for main operations |
155 - 276V |
 |
| Input voltage adjustable range for mains operation |
151 - 268V |
| Batteries & Runtime |
| Battery Type |
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
 |
| Typical recharge time |
3 hour(s) |
 |
| Replacement battery cartridge |
RBC55 |
 |
| RBC™ Quantity |
1 |
 |
| Typical Backup Time at Half Load |
17.0 minutes (1350 Watts) |
 |
| Typical Backup Time at Full Load |
5.0 minutes (2700 Watts) |
 |
| Runtime Chart |
Smart-UPS XL |
 |
| Extended Run Options |
APC Smart-UPS XL 3000VA 208V Tower/Rack Convertible |
| Communications & Management |
| Interface Port(s) |
DB-9 RS-232,SmartSlot |
 |
| Available SmartSlot™ Interface Quantity |
1 |
 |
| Control panel |
LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators |
 |
| Audible Alarm |
Alarm when on battery : distinctive low battery alarm : configurable delays |
 |
| Emergency Power Off (EPO) |
Optional |
| Surge Protection and Filtering |
| Surge energy rating |
480 Joules |
 |
| Filtering |
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
| Physical |
| Maximum Height |
17.00 inches (432 mm) |
 |
| Maximum Width |
7.70 inches (196 mm) |
 |
| Maximum depth |
19.80 inches (503 mm) |
 |
| Net Weight |
137.00 lbs. (62.27 kg) |
 |
| Shipping Weight |
167.00 lbs. (75.91 kg) |
 |
| Shipping Height |
22.00 inches (559 mm) |
 |
| Shipping Width |
15.00 inches (381 mm) |
 |
| Shipping Depth |
30.00 inches (762 mm) |
 |
| Color |
Black |
| Environmental |
| Operating Environment |
32 - 104 °F (0 - 40 °C) |
 |
| Operating Relative Humidity |
0 - 95% |
 |
| Operating Elevation |
0-10000 feet (0-3000 meters) |
 |
| Storage Temperature |
5 - 113 °F (-15 - 45 °C) |
 |
| Storage Relative Humidity |
0 - 95% |
 |
| Storage Elevation |
0-50000 feet (0-15000 meters) |
 |
| Audible noise at 1 meter from surface of unit |
53 dBA |
 |
| Online Thermal Dissipation |
275.00 BTU/hr |
| Conformance |
| Regulatory Approvals |
CSA,FCC Part 15 Class A,UL 1778 |
 |
| Standard Warranty |
2 years repair or replace,optional on-site warranties available,optional extended warranties available |
 |
| Equipment protection policy |
Lifetime : $150000 |